TRINIDAD AND TOBAGOPROJECT DESIGN

PROJECT DESIGN · TRINIDAD AND TOBAGO

Trinidad and Tobago EV Charging Pilot: Planning Around a Limited Grid Connection

01

Start with the pilot site

Picture two drivers arriving at the same time. One needs a quick top-up. The other will be parked for a while. At this proposed charging site in Trinidad and Tobago, where they stop matters as much as how much power they can draw.

The Trinidad and Tobago EV charging pilot brief lists three 120 kW DC fast chargers and two AC chargers. The customer reports a grid connection below 350 kVA. Those figures shape both the first site walk and the equipment order. The pilot would give the operator a chance to see how drivers actually use the bays before pricing a larger station.

02

Give short and long stays their own charging spaces

From the entrance, drivers making a short stop should be able to spot the DC bays and see where to wait if they’re full. Drivers staying longer can head to the AC bays. Where the site allows, the waiting area should sit clear of the entry lane and the routes vehicles use to leave a bay.

Walk the layout with the proposed charger locations in mind. Can a driver reach a vehicle inlet without crossing the next bay? Can an installer reach the equipment without closing the entry lane? The answers help the operator confirm bay layout, terminal count and cable reach with the site designer.

Design illustration of the pilot entrance and separate fast and longer-stay charging areas
03

Set the site power limit before choosing the chargers

The three proposed DC units have a combined rated output of 360 kW. A connection below 350 kVA cannot supply that full output at once, even before conversion losses, AC charging and other site loads are counted. Have the local electrical designer check the service capacity and set the import limit at the main supply point.

Design illustration of a protected meter and distribution area beside the proposed charging bays

EV charging load management starts with what the site draws at that point. The operator and installer can agree how the site controller will allocate the remaining capacity when DC and AC sessions overlap. Depending on the equipment, the controller may limit individual chargers or request a total power cap from a shared power unit.

Before equipment is ordered, ask the supplier to show how the proposed controls communicate with each charger. Agree what the system should do if a meter reading or communications link is lost, and include that behavior in acceptance testing. Our commercial EV charging installation guide covers the wider site preparation.

Concept diagram of the grid connection, import meter, site power control and pilot charging loads
04

Compare the pilot with a ten-position reference station

The customer also requested a separate ten-position station for budgeting. This option gives the operator a way to compare a larger equipment package and decide which parts belong in the initial purchase.

Requested charging station configurations
Planning itemGrid-connected pilotTen-position reference station
Charger mixThree 120 kW DC units and two AC units requestedSeven 120 kW DC units requested, with AC for the remaining positions
Electrical designVerify the reported connection and set a site limitSize the supply and transformer for agreed simultaneous use
Canopy and solarOpen charging areaCompare a plain canopy with a solar canopy
Short-duration backupCharger supply is the starting scopePrice separately once the protected loads and duration are agreed
Enquiry scopeCharger equipment and controls, with local installation separateCompare equipment, distribution, site works and options as separate items

The larger station brief favors a central power unit that can share capacity across terminals and a common monitoring platform. Ask for a power allocation example covering both a quiet period and a busy one. If the operator wants to assess a solar canopy or backup battery, use a separate scope to set the loads and operating hours. KUNETIC’s solar and storage charging solution can inform that discussion.

Two-column design comparison of the grid-connected pilot and a separate ten-position reference station

Pilot equipment budget

Allow US$12,000–20,000, FOB Shenzhen, for the three 120 kW DC chargers, two AC chargers and provision for site load management. Connector types, site voltage and the selected controls shape the final equipment quote.

Freight, import charges, site works, local electrical installation and grid connection are priced separately. Request a separate quote for the ten-position station and any canopy, solar or backup options.

05

Use the pilot data to decide when to expand

Once a pilot is operating, record arrival times, dwell time, energy delivered per session and how often more than one vehicle charges at once. Match those records to peak import and the periods when chargers reduce output. If drivers wait while chargers still have power available, look at the number of bays and how long vehicles stay. If several active chargers keep slowing down, check whether the site is hitting its import limit.

Those records can help the operator decide whether to revisit bay allocation, adjust the charger mix or request more grid capacity. Use those figures to compare the larger station against the number of drivers you want to serve at the busiest hour.

06

Bring your site details to a configuration review

Bring a recent service or transformer schedule, a site sketch and a list of other loads sharing the connection. Include the charger types you are considering, the time drivers usually stay and the number you expect to serve together at busy periods.

KUNETIC can use those inputs to discuss the equipment scope, controls and options with your local design team. Discuss your charging site with KUNETIC.

07

Frequently asked questions

Can all three 120 kW DC chargers run at full output together?

The combined DC output would be 360 kW, above the theoretical real power available from the reported connection. Plan the simultaneous output around the verified supply and the other loads the site must serve.

How is charging power shared at a busy site?

The site controller can use the agreed input limit and measured site load to set the charging allowance. The selected hardware and controls determine how that allowance is shared among active sessions.

Does the pilot include solar or a canopy?

The pilot brief calls for a grid-connected charger package with open bays. Plain and solar canopies are separate options for the ten-position reference station.

What should the operator measure before considering more chargers?

Record concurrent sessions, vehicle dwell time, energy per visit, peak import and periods of reduced output. Use these records to identify whether the bottleneck is space, charging power or the grid connection.

COMMERCIAL CHARGING PROJECTS

Plan Your
Charging Site

Share your electrical supply, bay layout and expected charging demand.

Design illustration of a protected meter and distribution area beside the proposed charging bays
Visit our contact page

Plan Your Charging Site

Share your electrical supply, bay layout and expected charging demand.

Minimum 10 characters.

Drag & Drop a Project File Here

PDF, JPG, PNG, WEBP, DOCX, XLSX or ZIP · Max 8 MB