Store surplus solar
In a site with AC-coupled rooftop PV, the PCS can charge the battery when solar output exceeds the facility's demand.
Outdoor C&I Battery Storage
Store surplus rooftop solar and use it when demand rises. This IP55 outdoor system combines 160.8 kWh of LFP storage, battery management, air cooling and a side-mounted bidirectional inverter (PCS) in one equipment package. Choose the inverter configuration around your site's AC supply and load profile.
Bring battery storage to the equipment yard and size the electrical package around the way your facility uses power.
Ten 16.08 kWh modules form a 512 V nominal battery string. Use the cabinet capacity to compare how much solar energy you can shift into the evening or reserve for periods of higher demand.
Locate the battery near the electrical equipment without using production floor space. Allow for service access, airflow and delivery when planning the equipment pad.
The cabinet houses the battery modules, BMS and air cooling. The bidirectional inverter mounts on the side of the cabinet and exchanges battery status and operating limits with the BMS.
The side-mounted inverter converts AC to DC to charge the battery and DC to AC to supply the site. Use your peak demand and the hours you want to cover to select the inverter configuration, then check the battery-side limits below.
| Check | Cabinet data | What to verify |
|---|---|---|
| DC voltage | 448–576 V DC | PCS input limits across the battery operating range |
| Battery current | 140 A rated | DC current at the intended operating point |
| Communications | CAN 2.0 | Supported BMS messages and limits on the proposed PCS |
Send the existing inverter model, site voltage, load profile and PV layout so we can review a suitable battery and PCS configuration.
In an AC-coupled solar project, the rooftop PV inverter feeds the site's AC distribution. The cabinet's side-mounted PCS manages power in both directions between the battery and that AC bus. Site metering and controls determine when the battery charges or discharges.
In a site with AC-coupled rooftop PV, the PCS can charge the battery when solar output exceeds the facility's demand.
The site controller can use meter readings to schedule discharge around demand peaks. Share interval data to see whether the peaks are brief or sustained.
Battery capacity in kWh helps size the amount of energy to shift. The AC power available at the site depends on the PCS, battery operating limits and project design.
An outdoor equipment area can keep the battery close to the point of connection while leaving space inside the building for operations.
Application concepts
Store daytime PV surplus for later use at workshops, food-processing sites or warehouses with evening loads.
Use recorded peak demand and tariff periods to decide how much energy the system should deliver during a production shift.
Review delivery access, mounting, clearances and cable routes before choosing the cabinet and PCS locations.
Technical Specifications
Engineering data from the product sheet.
| Battery chemistry | Lithium iron phosphate (LFP) |
| Nominal energy | 160.8 kWh |
| Module configuration | 10 × 16.08 kWh in series |
| Rated capacity | 314 Ah |
| Nominal system voltage | 512 V DC |
| Operating voltage range | 448–576 V DC |
| Rated charge/discharge current | 140 A |
| BMS communication | CAN 2.0 |
| Enclosure protection | IP55 |
| Thermal management | Air cooling |
| Power conversion | Side-mounted bidirectional inverter, configured for the project |
| Dimensions | 1,395 × 1,080 × 1,850 mm |
Downloads
Share the site voltage and intended operating mode to request the cabinet datasheet and side-mounted inverter configuration.
It is the nominal battery energy of one cabinet, made up of ten 16.08 kWh LFP modules. Energy delivered to the AC loads depends on the usable operating window, conversion losses and site settings.
The bidirectional PCS mounts on the side of the battery cabinet. Share your site voltage and load profile so we can match the PCS configuration to your project. The battery-side operating range is 448–576 V DC, with a rated current of 140 A and CAN 2.0 communication.
It can be considered for an AC-coupled retrofit. Share the existing inverter, meter arrangement and grid connection so the project team can review the integration.
The enclosure is rated IP55 and uses air cooling. Plan the installation area around airflow, service access, site drainage and cable routing.
Send your interval load data, target demand limit, tariff periods and available PV generation data. Peak duration and frequency help establish the battery and PCS sizes.
For distribution or repeat installations, share the project market, intended PCS, enclosure and labelling preferences, and expected quantities.
Discuss your requirements
Send your site voltage, location, load profile and existing or planned PV capacity. Include the PCS model if it has already been selected.